Standard on all Russelectric automatic transfer switches and bypass/isolation switches, this microprocessor-based system controls all operational functions of the automatic transfer switch, including standard accessories and user-specified optional accessories. 

 

Senses normal and emergency source voltages; indicates ATS position and CPU operation
Provides 3-phase over/under voltage, over/under frequency, phase sequence detection, and phase differential monitoring for both normal and emergency sources
Controller uses industry-standard open-architecture communications protocol for high-speed serial communications via multidrop connection to other controllers and to master terminal 
All control setup information, programs, and calibration data are stored in the unit's nonvolatile memory and saved in the event of a control power interruption
Rechargeable NiCad battery provide 5 VDC power to the controller during the engine start timing cycle when no AC or DC power is available
Self-diagnostics perform periodic checks of the memory, I/O and communications systems; invoke a software reset if error is detected
Watchdog timer circuit invokes hardware reset if program execution exceeds 1.6 seconds 
Accessory Setup and Services screen allows accessory installation and changes to system setup, calibration, and diagnostic functions

Model 2000  

 

 

 

 

 

 

 

 

 

 

 

Authorized password required for all setup and reset functions 

Click here for for information on the Model 2000 PLUS performance upgrade with extended power monitoring capabilities